OVR ABB 2CTB803973R1200 – 20kA тип 2+3 – ZAS-№001
OVR ABB 2CTB803973R1200 – 20kA тип 2+3
General Information
Extended Product Type:OVR T2-T3 3N 20-275 P QS
Product ID:2CTB803973R1200
Всички цени са за брой БЕЗ ДДС
Телефон за поръчки: 0887 799 134
За Количества Отстъпки
Technical
- Type of Low Voltage Distribution System:TT
- TN-S
- Nominal AC Voltage of the System (Uo):230 / 400 V
- Number of Protected Poles:4
- Arrester Class:II
- Product Main Type:T2-T3
- Standards:IEC 61643-11 / EN 61643-11
- Product Type:QS
- Version:Plug-in
- Discharge Current:Nominal 5 kA
- Maximum 20 kA
- Total 80 kA
- Impulse Current:I (imp, 10 / 350 µs) 2 kA
- Maximum Continuous Operating Voltage (Uc):(L-PE) 275 V
- (L-L) 440 V
- (L-N) 275 V
- (N-PE) 275 V
- Voltage Rating DC:350 V
- Voltage Protection Level ( Up):(L-N) 0.9 kV
- (N-PE) 1.4 kV
- (L-PE) – kV
- Short Circuit Withstand Icc:100 kA
- Temporary Overvoltage Test Value (UT):(L-N) 337 V
- (N-PE) 1200 V
- Short-Circuit Protective Devices:Curve B Breakers ≤ 125 A
- Curve C Breakers ≤ 125 A
- gL Type Fuses ≤ 125 A
- gG Type Fuses ≤ 125 A
- Auxiliary Circuit Load:Minimum –
- Maximum –
- Power Loss:29 mW
Suitable For:To protect the systems against the transient overvoltage (lightning)
Dimensions
- Product Net Width:71.2 mm
- Product Net Depth / Length:58 mm
- Product Net Height:88 mm
- Product Net Weight:0.48 kg
Width in Number of Modular Spacings:4