OVR ABB 2CTB803973R1200 – 20kA тип 2+3 – ZAS-№001

OVR ABB 2CTB803973R1200 – 20kA тип 2+3
General Information
Extended Product Type:OVR T2-T3 3N 20-275 P QS
Product ID:2CTB803973R1200

Всички цени са за брой БЕЗ ДДС
Телефон за поръчки: 0887 799 134
За Количества Отстъпки

    Бърза Заявка


    Technical

    • Type of Low Voltage Distribution System:TT
    • TN-S
    • Nominal AC Voltage of the System (Uo):230 / 400 V
    • Number of Protected Poles:4
    • Arrester Class:II
    • Product Main Type:T2-T3
    • Standards:IEC 61643-11 / EN 61643-11
    • Product Type:QS
    • Version:Plug-in
    • Discharge Current:Nominal 5 kA
    • Maximum 20 kA
    • Total 80 kA
    • Impulse Current:I (imp, 10 / 350 µs) 2 kA
    • Maximum Continuous Operating Voltage (Uc):(L-PE) 275 V
    • (L-L) 440 V
    • (L-N) 275 V
    • (N-PE) 275 V
    • Voltage Rating DC:350 V
    • Voltage Protection Level ( Up):(L-N) 0.9 kV
    • (N-PE) 1.4 kV
    • (L-PE) – kV
    • Short Circuit Withstand Icc:100 kA
    • Temporary Overvoltage Test Value (UT):(L-N) 337 V
    • (N-PE) 1200 V
    • Short-Circuit Protective Devices:Curve B Breakers ≤ 125 A
    • Curve C Breakers ≤ 125 A
    • gL Type Fuses ≤ 125 A
    • gG Type Fuses ≤ 125 A
    • Auxiliary Circuit Load:Minimum –
    • Maximum –
    • Power Loss:29 mW

    Suitable For:To protect the systems against the transient overvoltage (lightning)

    Dimensions

    • Product Net Width:71.2 mm
    • Product Net Depth / Length:58 mm
    • Product Net Height:88 mm
    • Product Net Weight:0.48 kg

    Width in Number of Modular Spacings:4

    Size UK US EU Japan
    XS 6 - 8 4 34 7
    S 8 -10 6 36 9
    M 10 - 12 8 38 11
    L 12 - 14 10 40 13
    XL 14 - 16 12 42 15
    XXL 16 - 28 14 44 17